2 adjustment elements – VEGA VEGAWAVE 63 - two-wire User Manual

Page 21

background image

6

.2 Adjustment elements

3

4

1

2

5

Fig. 12: Electronics and connection compartment - two-wire output

1

Potentiometer for switching point adaptation

2

DIL switch for mode adjustment

3

Ground terminal

4

Connection terminals

5

Control lamp

With the potentiometer you can adapt the switching point to the solid. It
is already preset and must only be modified in special cases.

By default, the potentiometer of VEGAWAVE 63 is set to the right stop
(> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight solids, turn
the potentiometer to the left stop (> 0.008 g/cm³ or 0.0003 lbs/in³).
VEGAWAVE

63 will thus be more sensitive and can detect light-weight

solids more reliably.

For instruments detecting solids in water, these settings are not
applicable. The switching point adaptation is preset and must not be
changed.

With the mode adjustment (min./max.) you can determine the output
current.

When using a signal conditioning instrument, always set the mode
switch to max. mode.

In this case, you select the requested mode according to the "Function
chart
" (max. - max. detection or overfill protection, min. - min.detection
or dry run detection) on the signal conditioning instrument.