VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual
Page 59
Status
code
Description according to Pro-
fibus standard
Possible cause
0 x 00
bad - non-specific
Flash-Update active
0 x 04
bad - configuration error
l Adjustment error
l Configuration error with PV-Scale (PV-Span too small)
l Unit irregularity
l Error in the linearization table
0 x 0C
bad - sensor failure
l Hardware error
l Converter error
l Leakage pulse error
l Trigger error
0 x 10
bad - sensor failure
l Measured value generation error
l Temperature measurement error
0 x 1f
bad - out of service constant
"
Out of Service" mode switched on
0 x 44
uncertain - last unstable value
Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)
0 x 48
uncertain substitute set
l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0 x 4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0 x 51
uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0 x 52
uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0 x 80
good (non-cascade) - OK
OK
0 x 84
good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)
0 x 89
good (non-cascade) - active ad-
visory alarm - low limited
Lo-Alarm
0 x 8a
good (non-cascade) - active ad-
visory alarm - high limited
Hi-Alarm
0 x 8d
good (non-cascade) - active cri-
tical alarm - low limited
Lo-Lo-Alarm
0 x 8e
good (non-cascade) - active cri-
tical alarm - high limited
Hi-Hi-Alarm
VEGAPULS
67 • Profibus PA
59
10 Supplement
32940
-EN
-100514