If there is danger of strong buildup or condensation, you can
set the instrument more insensitive by one rotary switch
position.

The "Function chart" shows how to select the switching
condition of the output.

The following settings apply to products with low conductivity
(<3 mS)

1

Fill the vessel until the shortest probe is covered approx.
1 cm

2

Switch on voltage supply

3

Set the A/B switch to mode A

4

Set the rotary switch to position "TEST min."

5

Turn the rotary switch slowly clockwise until the red LED
lights

The instrument is adapted to the medium, i.e. the transistor
blocks at max. level.

The following settings apply to products with low conductivity
(<3 mS)

1

Empty the vessel until the min. measuring electrode is only
covered approx. 1 cm

2

Switch on voltage supply

3

Set the A/B switch to mode B

4

Set the rotary switch to position "TEST max."

5

Turn the rotary switch slowly anticlockwise until the red
LED lights

The instrument is adapted to the medium, i.e. the transistor
blocks at min. level.

The following settings apply to products with low conductivity
(<3 mS)

1

Fill the vessel until the shortest probe is covered approx.
1 cm

2

Switch on voltage supply

3

Set the A/B switch to mode A

4

Set the rotary switch to position "TEST min."

5

Turn the rotary switch slowly clockwise until the red LED
lights

Level detection for max. sig-
nal

Level detection for min. signal

Pump control, A mode

VEGAKON

66 - with transistor output

17