VEGA VEGAFLEX 66 (-200…+400°C) 4 … 20 mA_HART four-wire User Manual
Page 39
Error
Cause
Removal
V
oltage supply
missing
C
heck cables for breaks; repair if
necessary
O
perating voltage
too low or load
resistance too
high
C
heck, adapt if necessary
C
urrent signal
greater than 22 mA
or less than
3.6
mA
O
scillator in the
sensor defective
E
xchange the instrument or send it in
for repair
I
n Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
T
he indicating and adjustment modules indicates faults via error codes
and text messages. The following table describes the error codes with
status according to NE 107 and gives information on the causes of
failure and their removal:
Status accor-
ding to NE 107
Error code
Text message
Cause/Rectification
F
ailure
E
013
no measured value available
S
ensor in boot phase
no measured value available
S
ensor does not find an echo, e.g.
due to faulty installation or wrong
parameter adjustment
no measured value available
W
rong sensor length entered
E
017
A
djustment span too small
A
djustment not within the specifica-
tion. Carry out the adjustment again,
increasing the distance between
min. and max. adjustment
E
036
N
o operable software
F
ailed or interrupted software up-
date/Repeat software update
E
042
H
ardware error, electronics defec-
tive
E
xchange the instrument or send it
in for repair
E
043
H
ardware error, electronics defec-
tive
E
xchange the instrument or send it
in for repair
D
epending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.
Error messages via the
indicating and adjust-
ment module
Reaction after fault rec-
tification
VEGAFLEX
66 • 4 … 20
mA/HART four-wire
39
8 M
aintenance and fault rectification
34174
-