Input variable
Measured variable
distance between process fitting and product sur-
face
Min. distance from antenna end
50 mm (1.969 in)
6)
Measuring range
up to 15 m (49.21 ft)
Reference conditions to measuring accuracy (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
-
Temperature
+18
… +30 °C (+64 … +86 °F)
-
Relative humidity
45 … 75 %
-
Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Other reference conditions
-
Reflector
ideal reflector, e.g. metal plate 2 x 2 m
-
False reflections
Largest false echo 20 dB smaller than the useful
echo
Characteristics and performance data
Frequency
K-band
Interval
approx. 1 s
Beam angle -3 dB
7)
10°
Step response or adjustment time
8)
> 1
s (dependent on the parameter setting)
Max. level change
Adjustable up to 1 m/min. (dependent on the
parameter settings)
Max. emitted HF power of the antenna system
-
Pulse peak power
< 10
mW
-
Pulse duration
< 2
ns
-
Average power
< 25 µW
-
Average power with 1 m distance
< 1 µW/
cm
2
Measuring accuracy
Resolution, general
max. 1 mm (0.039 in)
Deviation
9)
see diagrams
6)
In products with low dielectric value up to 50 cm (19.69 in).
7)
Corresponds to the range with 50 % of the emitted power
8)
Time to output the correct level (with max. 10 % deviation) after a sudden
level change.
9)
Incl. non-linearity, hysteresis and non-repeatability.