VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 49

Error
Cause
Removal
When an additio-
nal instrument is
connected, the H1
segment fails.
Max. supply cur-
rent of the seg-
ment coupler
exceeded
Measure the current consumption,
reduce size of segment
Measured value
on the indicating
and adjustment
module does not
correspond to the
value in the PLC
The menu item
"
Display - Dis-
play value
"
is
not set to "
AI-
Out
"
Check values and correct, if neces-
sary
Instrument does
not appear during
connection setup
Profibus DP cab-
le pole-reversed
Check cable and correct, if necessary
Incorrect termina-
tion
Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification
Instrument not
connected to the
segment
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or
wrong parameter adjustment
?
E
017
l
Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E
036
l
no operable sensor software
à Carry out a software update or send instrument for repair
?
E
041, E042, E043
l
Hardware error, electronics defective
à Exchange the instrument or send it in for repair
Error messages via the