VEGA VEGAFLEX 66 (-110…+400°C) 4 … 20 mA_HART - four-wire User Manual
Page 27
Caution:
I
f there is a separation of different liquids in the vessel, e.g. by
condensation, VEGAFLEX 66 will always detect the medium
with the higher dielectric figure (ε
r
).
K
eep in mind that interfaces can cause faulty measurements.
I
f you want to measure the total height of both liquids reliably,
please contact our service department or use an instrument
specially designed for interface measurement.
S
tart your parameter adjustment with the following menu items
of the basic adjustment:
P
roceed as follows:
1 M
ove from the measured value display to the main menu
by pushing [OK].
▶
B
asic adjustment
D
isplay
D
iagnostics
S
ervice
I
nfo
2 S
elect the menu item "Basic adjustment" with [->] and
confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.
M
in. adjustment
0.00 %
=
10.000 m(d)
8.000
m(d)
3 P
repare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
T
he cursor jumps now to the distance value.
4 E
nter the suitable distance value in m for the empty vessel
(
e.g. distance from the sensor to the vessel bottom)
corresponding to the percentage value.
5 S
ave the settings with [OK] and move to "Max. adjustment"
with [->].
P
roceed as follows:
M
ax. adjustment
100.00 %
=
1.000 m(d)
2.000
m(d)
Carrying out min. ad-
justment
Carrying out max. ad-
justment
VEGAFLEX
66 • 4 … 20
mA/HART - four-wire
27
6 S
et up with the indicating and adjustment module PLICSCOM
32763
-
EN
-080826