VEGA VEGAPULS 65 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual
Page 36
Function
Reset value
Sensor address
126
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
5)
Medium
Liquid
Vessel form
not known
Damping
0 s
Linearisation
linear
Channel
PV lin. %
Sensor-TAG
Sensor
Displayed value
PA-Out
Extended settings
None
Additional PA value
Secondary Value 1 %
Out-Scale-Unit
%
PV-Out-Scale
0.00 lin-% = 0.0 %
100.0 lin-% = 100 %
Unit of measurement
m(d)
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
Function
Reset value
Sensor address
no reset
Language
no reset
Factory setting
Like basic adjustment, furthermore special parameters are reset to
default values.
6)
Pointer
The min. and max. distance values are reset to the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following menu
schematic. You will find a detailed description of these menu items in
the operating instructions manual "Indicating and adjustment module".
5)
Depending on the sensor type, see chapter "Technical data".
6)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.
Optional settings
36
VEGAPULS
65 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM