VEGA VEGASON 64 Profibus PA User Manual
Page 36
Note:
Since with the function "Quick level change > 1 m/min." the generation
of an average value of the signal processing is considerably reduced,
false reflections by agitators or vessel installations can cause
measured value fluctuations. A false echo memory is thus recom-
mended.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l
Measured value presentation
l
Adjustment
l
Medium
l
Vessel form
l
Damping
l
Linearisation curve
l
Sensor-TAG
l
Displayed value
l
Scaling unit (Out-Scale unit)
l
Positions after the decimal point (scaled)
l
Scaling PA/Out-Scale 4 values
l
Unit of measurement
l
Language
The following safety-relevant data are not read out or written:
l
Sensor address
l
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
2)
Function
Reset value
Sensor address
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
3)
Medium
Liquid
2)
Sensor-specific basic adjustment.
3)
Depending on the sensor type, see chapter "Technical data".
Copy sensor data
Reset
36
VEGASON
64 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM
28787
-EN
-081127