VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 65

background image

Byte-No.

1

2

3

4

5

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

Format

Value

Note:
Bytes 6-10 are not used in this example.

Data format of the output signal

Byte4

Byte3

Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 45: Data format of the output signal

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).

The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7
2

Significant

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Significant

-9

-10 -11 -12 -13 -14 -15 -16 -17

-18 -19

-20 -21 -22 -23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 46: Data format of the measured value

Coding of the status byte associated with the PA output value

Status
code

Description according to Pro-
fibus standard

Possible cause

0 x 00

bad - non-specific

Flash-Update active

0 x 04

bad - configuration error

l Adjustment error
l Configuration error with PV-Scale (PV-Span too small)
l Unit irregularity
l Error in the linearization table

VEGAPULS

62 • Profibus PA

65

10 Supplement

28445

-EN

-090305