VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual
Page 58
Gas phase
Temperature
1 bar/14.5 psig
10 bar/145 psig
50 bar/725 psig
Air/Nitrogen
20 °C/68 °F
0.00 %
0.22 %
1.2 %
Air/Nitrogen
200 °C/392 °F
0.00 %
0.13 %
0.74 %
Hydrogen
20 °C/68 °F
-0.01 %
0.10 %
0.61 %
Hydrogen
200 °C/392 °F
-0.02 %
0.05 %
0.37 %
Water (saturated
steam)
100 °C/212 °F
0.20 %
-
-
Water (saturated
steam)
180 °C/356 °F
-
2.1 %
-
Ambient conditions
Ambient, storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process temperature (measured on the process fitting), depending on seal and antenna system
-
FKM (Viton)
-40 … +130 °C (-40 … +266 °F)
-
FFKM (Kalrez 6375)
-20 … +130 °C (-4 … +266 °F)
-
FKM (Viton) with temperature adapter
-40 … +200 °C (-40 … +392 °F)
-
FFKM (Kalrez 6375) with temperature
adapter
-20 … +200 °C (-4 … +392 °F)
-
FFKM (Kalrez 2035, 6230) (FDA)
-15 … +130 °C (+5 … +266 °F)
-
FFKM (Kalrez 2035, 6230) (FDA) with
temperature adapter
-15 … +200 °C (+5 … +392 °F)
-
FKM (Viton) with impedance cone PP
-40 … +80 °C (-40 … +176 °F)
-
FFKM (Kalrez 6375) with impedance
cone PP
-15 … +80 °C (+5 … +176 °F)
For the vessel pressure, you also have to note the specifications on the type label. Always the
lowest value is applicable.
Vessel pressure - horn antenna
-1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psi)
Vessel pressure - parabolic antenna
-1 … 6 bar/-100 … 6000 kPa (-14.5 … 870 psi)
Vessel pressure relating to the flange nom-
inal stage
see supplementary instructions manual "Flanges
according to DIN-EN-ASME-JIS"
Vibration resistance
9)
-
Horn antenna
mechanical vibrations with 4 g and 5 … 100 Hz
-
Parabolic antenna
mechanical vibrations with 1 g and 5 … 100 Hz
Data on rinsing air connection
Pressure
<
6 bar (87.02 psi)
Air quantity see diagram
9)
Tested according to the regulations of German Lloyd, GL directive 2.
58
VEGAPULS
62 • Profibus PA
10 Supplement
28445
-EN
-090305