beautypg.com

VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 19

background image

d

h

max.

d

1½"
50 mm/2"
80 mm/3"
100 mm/4"
150 mm/6"

200 mm
250 mm
300 mm
500 mm
800 mm

h

max.

Fig. 11: Deviating socket dimensions

Tip:
VEGAPULS

62 is optionally also available with antenna extension.

Hence the antenna length can be selected such that the antenna end
protrudes 10 mm (0.4 in) out of the socket.

Align the sensor in liquids as vertical as possible to the product surface
to achieve optimum measuring results.

Fig. 12: Alignment in liquids

The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the microwave signals.

Vessel installations such as, for example, ladders, limit switches,
heating spirals, struts, etc. can cause false echoes that get super-
imposed on the useful echo. Make sure when planning your measuring
site that the radar sensor has a "clear view" to the measured product.

In case of existing vessel installations, a false echo storage should be
carried out during setup.

If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.

Sensor orientation

Vessel installations

VEGAPULS

62 • Profibus PA

19

4 Mounting

28445

-EN

-090305