5 connecting to power supply, 1 preparing the connection, 2 connection procedure – VEGA VEGASWING 61 - Relay (DPDT) User Manual
Page 14
14
5 Connecting to power supply
VEGASWING 61 • - Relay (DPDT)
29224-EN-130409
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
•
Connect only in the complete absence of line voltage
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
Connect the operating voltage according to the connection diagrams.
The electronics module with relay output is designed in protection
class I. To maintain this protection class, it is absolutely necessary
that the earth conductor is connected to the inner earth conductor
terminal. Keep the general installation regulations in mind. Take note
of the corresponding installation regulations for hazardous areas with
Ex applications.
The data for power supply are specified in chapter "Technical data".
The instrument is connected with standard three-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Use cable with round cross-section. A cable outer diameter of
5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.
If you are using cable with a different diameter or cross-section,
exchange the seal or use a suitable cable gland.
In hazardous areas, only use approved cable connections for VEGAS-
WING 61.
Take note of the corresponding installation regulations for Ex applica-
tions.
Cover all housing openings conforming to standard according to
EN 60079-1.
5.2 Connection procedure
With Ex instruments, the housing cover may only be opened if there is
no explosive atmosphere present.
Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nut of the cable entry
3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
4. Insert the cable into the sensor through the cable entry
5. Open the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Tighten the terminals with a screwdriver
Note safety instructions
Take note of safety
instructions for Ex
applications
Voltage supply
Connection cable
Connection cable
for Ex applications