4 Mounting

VEGASWING 61 • - Relay (DPDT)

29224-EN-130409

4 Mounting

4.1 General instructions

Make sure that all parts of the instrument coming in direct contact with

the process, especially the sensor element, process seal and process

fitting and suspension cable, are suitable for the existing process

conditions, such as process pressure, process temperature as well as

the chemical properties of the medium.
You can find the specifications in chapter "Technical data" and on the

type plate.

In general, VEGASWING 61 can be installed in any position. The

instrument only has to be mounted in such a way that the tuning fork

is at the height of the desired switching point.
The tuning fork has lateral markings (notches) that indicate the

switching point with vertical mounting. The switching point refers

to water with the basic setting of the sensitivity switch ≥ 0.7 g/cm³

(0.025 lbs/in³). When mounting VEGASWING 61, make sure that

this marking is at the height of the requested switching point. Keep in

mind that the switching point of the instrument is shifted if the medium

has a density other than water - water 1 g/cm³ (0.036 lbs/in³). For

products < 0.7 g/cm³ (0.025 lbs/in³) and > 0.5 g/cm³ (0.018 lbs/in³)

the density switch must be set to ≥ 0.5 g/cm³.
Keep in mind that foams with a density > 0.45 g/cm³ (0.016 lbs/in³)

are detected by the sensor. This can cause faulty switchings particu-

lary when used as dry run protection system.

2

3

1

4

Fig. 2: Mounting vertical
1 Switching point approx. 13 mm (0.51 in)

2 Switching point with lower density

3 Switching point with higher density

4 Switching point approx. 27 mm (1.06 in)

Suitability for the process

conditions

Switching point