beautypg.com

VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART four-wire User Manual

Page 44

background image

V

essel pressure relating to the flange nom-

inal stage

see supplementary instructions manual "Flanges
according to DIN-EN-ASME-JIS
"

V

ibration resistance

mechanical vibrations with 1 g and 5 … 100 Hz

9)

Electromechanical data - version IP 66/IP 67

C

able entry

-

D

ouble chamber housing

l

1

x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),

1

x blind stopper M20 x 1.5; plug M12 x 1 for

VEGADIS

61 (

optional)

or:

l

1

x closing cap ½ NPT, 1 x blind stopper

½

NPT,

plug M12 x 1 for VEGADIS 61

(

optional)

or:

l

1

x plug (depending on the version), 1 x blind

stopper M20 x 1.5; plug M12 x 1 for VEGADIS
61 (

optional)

S

pring-loaded terminals for wire cross-sec-

tion

2.5

mm² (AWG 14)

Indicating and adjustment module

V

oltage supply and data transmission

through the sensor

I

ndication

LC

display in dot matrix

A

djustment elements

4

keys

P

rotection

-

unassembled

IP

20

-

mounted into the sensor without cover

IP

40

M

aterials

-

H

ousing

ABS

-

I

nspection window

P

olyester foil

Power supply

O

perating voltage

-

N

on-Ex and Ex-d instrument

20 … 72 V DC, 20 … 253 V AC, 50/60 H

z

M

ax. power consumption

4 VA; 2.1 W

Electrical protective measures

P

rotection

IP

66/IP 67

O

vervoltage category

III

P

rotection class

I

9)

T

ested according to the regulations of German Lloyd, GL directive 2.

44

VEGAPULS

66

standpipe version • 4 … 20 mA/HART four-wire

10 S

upplement

28742

-EN

-090305