M

edium

Liquid
Water based
Acids/Bases

E

nter the requested parameter via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

part from the medium, the vessel shape can also influence the

measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Liquids" these are "Storage tank", "Stilling tube",
"

Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".

V

essel form

Storage tank

E

nter the requested parameter via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e. g. with a cylindrical or
spherical tank - and the indication or output of the volume is required.
C

orresponding linearization curves are preprogrammed for these

vessels. They represent the correlation between the level percentage
and vessel volume. By activating the appropriate curve, the volume
percentage of the vessel is displayed correctly. If the volume should
not be displayed in percent but e.g. in l or kg, a scaling can be also set
in the menu item "Display".

L

inearisation curve

linear

E

nter the requested parameter via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

H

igh sockets or vessel installations, such as e. g. struts or agitators as

well as buildup and weld joints on the vessel walls cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections will
be detected.

Vessel form

Linearisation curve

Gating out of false sig-
nals

26

VEGAPULS

66

standpipe version • 4 … 20 mA/HART four-wire

6 S

et up with the indicating and adjustment module PLICSCOM