nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A
part from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Liquids" these are "Storage tank", "Stilling tube",
"
Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".
V
essel form
Storage tank
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A
linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e. g. with a cylindrical or
spherical tank - and the indication or output of the volume is required.
C
orresponding linearization curves are preprogrammed for these
vessels. They represent the correlation between the level percentage
and vessel volume. By activating the appropriate curve, the volume
percentage of the vessel is displayed correctly. If the volume should
not be displayed in percent but e.g. in l or kg, a scaling can be also set
in the menu item "Display".
L
inearisation curve
linear
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
H
igh sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections will
be detected.
Vessel form
Linearisation curve
Gating out of false sig-
nals