30

6 Set up with the display and adjustment module PLICSCOM

VEGASON 62 • 4 … 20 mA/HART - two-wire

28776-EN-130417

Extended setting

quick level change > 1 m/min.

Note:

Since with the function "Quick level change > 1 m/min." the genera-

tion of an average value of the signal processing is considerably

reduced, false reflections by agitators or vessel installations can

cause measured value fluctuations. A false echo memory is thus

recommended.

This function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the display

and adjustment module. A description of the function is available in

the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:

Measured value presentation

Adjustment

Medium

Vessel form

Damping

Linearization curve

Sensor-TAG

Displayed value

Display unit

Scaling

Current output

Unit of measurement

Language

The following safety-relevant data are not read out or written:

HART mode

PIN

Copy sensor data

Copy sensor data?

Basic adjustment

If the function "Reset" is carried out, the sensor resets the values of

the following menu items to the reset values (see chart):

1)

Function

Reset value

Sensor address

126

Max. adjustment

0 m(d)

Min. adjustment

Meas. range end in m(d)

2)

Medium

Liquid

Copy sensor data

Reset

1)

Sensor-specific basic adjustment.

2)

Depending on the sensor type, see chapter "Technical data".