6 Set up with the display and adjustment module PLICSCOM
VEGASON 62 • 4 … 20 mA/HART - two-wire
28776-EN-130417
Extended setting
quick level change > 1 m/min.
Note:
Since with the function "Quick level change > 1 m/min." the genera-
tion of an average value of the signal processing is considerably
reduced, false reflections by agitators or vessel installations can
cause measured value fluctuations. A false echo memory is thus
recommended.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
•
Measured value presentation
•
Adjustment
•
Medium
•
Vessel form
•
Damping
•
Linearization curve
•
Sensor-TAG
•
Displayed value
•
Display unit
•
Scaling
•
Current output
•
Unit of measurement
•
Language
The following safety-relevant data are not read out or written:
•
HART mode
•
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of
the following menu items to the reset values (see chart):
1)
Function
Reset value
Sensor address
126
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
2)
Medium
Liquid
Copy sensor data
Reset
1)
Sensor-specific basic adjustment.
2)
Depending on the sensor type, see chapter "Technical data".