beautypg.com

VEGA VEGASON 62 4 … 20 mA_HART - two-wire User Manual

Page 27

background image

27

6 Set up with the display and adjustment module PLICSCOM

VEGASON 62 • 4 … 20 mA/HART - two-wire

28776-EN-130417

Start your parameter adjustment with the following menu items of the

basic adjustment:

Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

Basic adjustment
Display
Diagnostics
Service
Info

2. Select the menu item "Basic adjustment" with [->] and confirm

with [OK]. Now the menu item "Min. adjustment" is displayed.

Min. adjustment
0.00 %
=
5.000 m(d)

4.000 m(d)

3. Prepare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value

with [+] and save with [OK]. The cursor jumps now to the distance

value.

4. Enter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to

the percentage value.

5. Save the settings with [OK] and move to "Max. adjustment" with

[->].

Proceed as follows:

Max. adjustment
100.00 %
=
1.000 m(d)

2.000 m(d)

1. Prepare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value

with [+] and save with [OK]. The cursor jumps now to the distance

value.

2. Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.

level must lie below the dead band.

3. Save the settings with [OK] and move to "Medium selection" with

[->].

Each product has different reflective properties. In addition, there

are various interfering factors which have to be taken into account:

agitated product surfaces and foam generation (with liquids); dust

generation, material cones and echoes from the vessel wall (with

solids). To adapt the sensor to these different conditions, you should

first select "Liquid" or "Solid".

Carry out min. adjustment

Carry out max. adjust-

ment

Medium selection