6 Set up with the display and adjustment module PLICSCOM
VEGASON 62 • 4 … 20 mA/HART - two-wire
28776-EN-130417
Start your parameter adjustment with the following menu items of the
basic adjustment:
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing [OK].
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Select the menu item "Basic adjustment" with [->] and confirm
with [OK]. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save the settings with [OK] and move to "Max. adjustment" with
[->].
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1. Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3. Save the settings with [OK] and move to "Medium selection" with
[->].
Each product has different reflective properties. In addition, there
are various interfering factors which have to be taken into account:
agitated product surfaces and foam generation (with liquids); dust
generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
first select "Liquid" or "Solid".
Carry out min. adjustment
Carry out max. adjust-
ment
Medium selection