VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART two-wire User Manual
Page 29
▶
B
asic adjustment
D
isplay
D
iagnostics
S
ervice
I
nfo
2
S
elect the menu item "Basic adjustment" with [->] and confirm with
[OK]
. N
ow the menu item "Min. adjustment" is displayed.
M
in. adjustment
0.00 %
=
5.000 m(d)
4.000
m(d)
3
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
E
nter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
S
ave the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
P
roceed as follows:
M
ax. adjustment
100.00 %
=
1.000 m(d)
2.000
m(d)
1
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
E
nter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
S
ave the settings with [OK] and move to "Medium selection" with
[->]
.
E
ach product has different reflective properties.
A
ccording to the conductivity and the dielectric value of liquids, the
reflection properties can differ considerably. Therefore additional
options such as "Solvent", "Chem. mixture" and "Water based" are
offered below the menu item Liquid.
T
hrough this additional selection, the sensor is adapted perfectly to the
product and measurement reliability, particularly in products with bad
reflective properties, is considerably increased.
Carrying out max. ad-
justment
Medium selection
VEGAPULS
62
standpipe version • 4 … 20 mA/HART two-wire
29
6 S
et up with the indicating and adjustment module PLICSCOM
28737
-EN