VEGA VEGASON 65 4 … 20 mA_HART four-wire User Manual
Page 33
0.00 %
=
5.000 m(d)
4.000
m(d)
3
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
E
nter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
S
ave the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
P
roceed as follows:
M
ax. adjustment
100.00 %
=
1.000 m(d)
2.000
m(d)
1
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
E
nter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
S
ave the settings with [OK] and move to "Medium selection" with
[->]
.
E
ach product has different reflective properties. In addition, there are
various interfering factors which have to be taken into account:
agitated product surfaces and foam generation (with liquids); dust
generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
fi
rst select "Liquid" or "Solid".
M
edium
Liquid
W
ith solids, you can also choose between "Powder/Dust", "Granular/
Pellets" or "Ballast/Pebbels".
T
hrough this additional selection, the sensor is adapted perfectly to the
product and measurement reliability, particularly in products with bad
reflective properties, is considerably increased.
Carrying out max. ad-
justment
Medium selection
VEGASON
65 • 4 … 20
mA/HART four-wire
33
6 S
et up with the indicating and adjustment module PLICSCOM
28782
-
EN
-081127