Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

Ʋ Reflector

ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)

Ʋ False reflections

Biggest false signal, 20 dB smaller than the useful signal

Measuring characteristics
Ultrasonic frequency

55 kHz

Interval

> 2 s (dependent on the parameter adjustment)

Abstrahlwinkel at -3 dB

11°

Adjustment time

5)

> 3 s (dependent on the parameter adjustment)

Measuring accuracy
Resolution, general

max. 1 mm

Deviation

6)

see diagram

16 mm (0.63 in)

-16 mm (-0.63 in)

5 m

(16.404 ft)

6 m

(19.685 ft)

7 m

(22.966 ft)

8 m

(26.247 ft)

4 m

(13.123 ft)

3 m

(9.843 ft)

2 m

(6.562 ft)

1 m

(3.28 ft)

10 mm (0.394 in)

4 mm (0.157 in)

-10 mm (-0.394 in)

-4 mm (-0.157 in)

Fig. 28: Deviation VEGASON 62

Influence of the ambient temperature to the sensor electronics

7)

Average temperature coefficient of the

zero signal (temperature error)

0.06 %/10 K

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

-20 … 200 kPa/-0.2 … 2 bar (-2.9 … 29 psig)

5)

Time to output the correct level (with max. 10 % deviation) after a sudden level change.

6)

Incl. non-linearity, hysteresis and non-repeatability.

7)

Relating to the nominal measuring range.