beautypg.com

3 exchanging the electronics module – VEGA VEGASON 62 Foundation Fieldbus User Manual

Page 36

background image

36

8 Maintenance and fault rectification

VEGASON 62 • Foundation Fieldbus

28791-EN-130417

Error

Cause

Rectification

Instrument does

not appear during

connection setup

Profibus DP cable

pole-reversed

Check cable and correct, if necessary

Incorrect termi-

nation

Check termination at the beginning

and end points of the bus and termi-

nate, if necessary, according to the

specification

Instrument not

connected to the

segment

Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

Error code Cause

Rectification

E013

no measured value

available

– Sensor in boot phase

– Sensor does not find an echo, e.g.

due to faulty installation or wrong

parameter adjustment

E017

Adjustment span too

small

– Carry out a fresh adjustment and

increase the distance between min.

and max. adjustment

E036

no operable sensor

software

– Carry out a software update or send

instrument for repair

E041

Hardware error, elec-

tronics defective

– Exchange the instrument or send it

in for repair

E113

Communication con-

flict

– Exchange the instrument or send it

in for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module

with respective Ex approval may be used.
If there is no electronics module available on site, one can be ordered

from the VEGA agency serving you.

The new electronics module must be loaded with the settings of the

sensor. These are the options:

At the factory by VEGA

Or on site by the user

In both cases, the sensor serial number is necessary. The serial num-

bers are stated on the type label of the instrument, inside the housing

or on the delivery note.

Error messages via the

display and adjustment

module

Reaction after fault recti-

fication

Sensor serial number