beautypg.com

5 menu schematic, Basic adjustment, Reset – VEGA VEGACAL 65 4 … 20 mA_HART - two-wire User Manual

Page 29

background image

29

6 Set up with the display and adjustment module PLICSCOM

VEGACAL 65 • 4 … 20 mA/HART - two-wire

30033-EN-130917

Basic adjustment

If the function "Reset" is carried out, the sensor resets all settings to

default.
The following values will be reset:

Function

Reset value

Max. adjustment

3000 pF

Min. adjustment

0 pF

Damping ti

0 s

Linearization

Linear

Sensor-TAG

Sensor

Display

%

Current output - characteristics

4 … 20 mA

Current output - max. current

20.5 mA

Current output - min. current

3.8 mA

Current output - failure

< 3.6 mA

Special parameters

All special parameters are reset to delivery status.
Peak value

The min. and max. values are reset to the actual value.

6.5 Menu schematic

Basic adjustment

Basic adjustment

1

Display
Diagnostics
Service
Info

Min. adjustment

1.1

0.00 %
=
0.0 pF
82.5 pF

Max. adjustment

1.2

100.00 %
=
1000.0 pF
327.4 pF

Damping

1.3

0 s

Linearization curve

1.4

Linear

Sensor-TAG

1.5

Sensor

Reset