6 Set up with the display and adjustment module PLICSCOM

VEGACAL 66 • Foundation Fieldbus

30038-EN-130917

– Save value

[->] key to select:

– Menu change

– Select list entry

– Select editing position

[+] key:

– Change value of the parameter

[ESC] key:

– Interrupt input

– Jump to next higher menu

The sensor is adjusted via the four keys of the display and adjust-

ment module. The LC display indicates the individual menu items. The

functions of the individual keys are shown in the above illustration.

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.4 Setup steps

After VEGACAL 66 is connected to voltage supply or after voltage

recurrence, the instrument carries out a self-check for approx. 30

seconds. The following steps are carried out:

Internal check of the electronics

Indication of the instrument type, the firmware as well as the sen-

sor TAGs (sensor designation)

Status byte goes briefly to fault value

Then the current measured value will be displayed and the corre-

sponding digital output signal will be outputted to the cable.

1)

VEGACAL 66 measures the capacitance of the respective product. To

display the actual level of the product, an allocation of the measured

capacitance to the percentage height must be carried out. For this

adjustment, the capacitance is entered with emptied and filled vessel.
If the vessel cannot be emptied or filled completely, you can carry out

the adjustment also with two known levels - for example with 10 %

and 90 %. The difference between the empty and full adjustment

values should be as large as possible.
The actual level can then be calculated on the basis of these settings.
VEGACAL 66 must be installed. A change of level is necessary for

this adjustment.
In the main menu item "Basic adjustment", the individual submenu

items should be selected one after the other and provided with the

correct parameter values.

Adjustment system

Switch-on phase

Parameter adjustment

1)

The values correspond to the actual measured level as well as to the settings

already carried out, e.g. default setting.