VEGA VEGACAP 63 - contactless electronic switch User Manual
Page 30
30
9 Supplement
VEGACAP 63 • - contactless electronic switch
30009-EN-130916
Modes (switchable)
Min./Max.
Switching delay
Ʋ When immersed
0.7 s
Ʋ When laid bare
0.7 s
Ʋ In case of failure
1 s
Ambient conditions
Ambient temperature on the housing
-40 … +80 °C (-40 … +176 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process pressure
Ʋ Threaded versions
-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-
pending on the process fitting
Ʋ Flange version
-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-
pending on the process fitting
Ʋ Flange version ≥ 3"/DN 80, plated
-0.4 … 64 bar/-40 … 6400 kPa (-5.8 … 928 psig), de-
pending on the process fitting
Process temperature VEGACAP 63 of 316L
Ʋ Insulation PE
-40 … +80 °C (-40 … +176 °F)
Ʋ Insulation PTFE
-50 … +150 °C (-58 … +302 °F)
Process temperature (thread or flange
temperature) with temperature adapter
(option with PTFE)
-50 … +200 °C (-58 … +392 °F)
1
2
3
-50°C
(-58°F)
50°C
(122°F)
40°C
(104°F)
-40°C
(-40°F)
80°C
(176°F)
0°C
(32°F)
100°C
(212°F)
150°C
(302°F)
200°C
(392°F)
Fig. 30: Ambient temperature - Process temperature
1 Process temperature
2 Ambient temperature
3 Temperature range with temperature adapter
Dielectric constant
≥ 1.5
Electromechanical data
Cable entry/plug (dependent on the version)