VEGA VEGACAP 63 - contactless electronic switch User Manual
Page 20
20
6 Setup
VEGACAP 63 • - contactless electronic switch
30009-EN-130916
You can adapt the switching point to the solid with the potentiometer.
With the potentiometer (1) and the measuring range selection switch
(2) you can change the sensitivity of the probe to the electrical proper-
ties of the product and the conditions in the vessel. This is necessary
so that the level switch can also reliably detect products e.g. with very
low or very high dielectric figure.
range 1: 0 … 20 pF
Range 2: 0 … 85 pF
Range 3: 0 … 450 pF
With the mode switch (3) you can change the switching status of the
output. The required mode can be set according to the function chart.
max. - max. detection or overfill protection
min. - min. detection or dry run protection.
We recommend connecting according to the quiescent current prin-
ciple (contactless electronic switch is open when the switching point
is reached) because the contactless electronic switch takes on the
same (safe) condition if a failure is detected.
Control lamp for indication of the switching status
•
green = switch closed
•
red = switch open
•
red (flashing) = failure
The adjustment of the switching point is only possible in installed
condition.
The specifications in parenthesis refer to the preceding illustration.
Horizontally mounted probes, angled probes
1. Set mode switch (3) to mode max [min.].
2. Set meas. range selection switch (2) to range 1.
3. Make sure the probe is not covered by the medium.
4. Turn the potentiometer (1) to 0, the control lamp (6) lights red
[lights green].
5. To determine the empty switch point, turn the potentiometer (1)
very slowly clockwise until the control lamp lights green [lights
red]. If the control lamp still lights red [lights green], then you have
to set the meas. range selection switch (2) to the next higher
stage and repeat the setting with the potentiometer (1) until the
control lamp lights green [lights red].
6. Note the position of the potentiometer (1).
In some cases the lowest range (range 1 = highest sensitivity)
is not sufficient to adjust the full switch point. This would make
another filling procedure necessary.
For this reason we recommend setting and noting the empty
switching point in all three meas. ranges. Set the meas. range se-
Switching point adapta-
tion (1)
Measuring range selec-
tion switch (2)
Mode adjustment (3)
Signal lamp (6)
Switching point adjust-
ment
Mode max. [mode min.]