beautypg.com

3 adjustment – VEGA VEGAVIB 66 - two-wire User Manual

Page 9

background image

Typical applications are overfill and dry run protection. Thanks

to its simple and robust measuring system, VEGAVIB 66 is

virtually unaffected by the chemical and physical properties of

the solid.
It functions even when exposed to strong external vibration or

changing products.
Solid detection in water

If VEGAVIB 66 was ordered for solid detection in water, the

tuning fork is to the density of water. In air or if covered by

water (density: 1 g/cm³/0.036 lbs/in) VEGAVIB 66 signals

uncovered. Only if the vibrating element is also covered with

solids (e.g. sand, sludge, gravel etc.) will the sensor signal

covered.
Fault monitoring

The electronics of VEGAVIB 66 continuously monitors the

following criteria:

l

Correct vibrating frequency

l

Line break to the piezo drive

If one of these faults is detected, the electronics signals this via

a defined current to the signal conditioning instrument. The

connection cable to the vibrating element is also monitored.

The tuning fork is piezoelectrically energised and vibrates at its

mechanical resonance frequency of approx. 150 Hz. When the

tuning fork is submerged in the product, the vibration

amplitude changes. This change is detected by the integrated

oscillator and converted into a switching command.

Depending on your requirements, VEGAVIB 66 with two-wire

electronics can be connected to different signal conditioning

instruments. Compatible signal conditioning instruments are

listed under "Technical data".
The exact range of the supply voltage is also specified in the

"Technical data" in the "Supplement".

3.3 Adjustment

With the factory setting, products with a density of >0.02 g/cm³

(>0.0008 lbs/in³) can be measured. It is possible to adapt the

instrument for products with lower density >0.008 g/cm³

(>0.0003 lbs/in³).
On the electronics module you will find the following indicating

and adjustment elements:

Physical principle

Power supply

VEGAVIB 66 - with two-wire output

9

Product description

29292

-EN

-060508