10.2 Profibus PA

Instrument master file

The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.

These data are, e.g. the permissible transmission rates as well as information on diagnostics values

and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-

cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-

ment in the configuration tool.

Ident number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. For VEGACAL 62

the ID number is 0x076E(hex) and the GSD file CL__076E.GSD. Optionally to this manufacturer-

specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGACAL 62

you have to use the general GSD file PA139700.GSD. If the general GSD file is used, the sensor

must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-

ates with the manufacturer-specific ID number.

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-

tion. The below block diagram below shows which data can be accessed by the PLC.

pF

%

Lin%

Min-Max

adjustment

Linearization

PROFIBUS PA-output

Primary

Value

Secondary

Value 2

Secondary

Value 1

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

TB

FB

Select additional cyclic

value

Fig. 25: VEGACAL 62: Block diagram with AI (PA-OUT) value and additional cyclical value
TB Transducer Block

FB Function Block

Module of the PA sensors

For the cyclic data traffic, VEGACAL 62 provides the following modules:

AI (PA-OUT)