4 Mounting

VEGASON 63 • 4 … 20 mA/HART - four-wire

28780-EN-130417

is expected. In this case, we recommend repeating a false echo stor-

age later with existing buildup.

1

2

> 200 mm

Fig. 5: Mounting on round vessel tops
1 Reference plane

2 Vessel center or symmetry axis

In vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible

down to the lowest point of the vessel bottom.

Fig. 6: Vessel with conical bottom

Preferably the transducer should be mounted flush to the vessel top.
If the reflective properties of the medium are good, you can mount

VEGASON 63 on a socket piece. You will find recommended values

for socket heights in the following illustration. The socket end should

be smooth and burr-free, if possible also rounded. Carry out a false

echo storage.

Socket