Setup – VEGA D84 Hydrostatic pressure transmitter User Manual
Page 31
Pressure transmitter D84
31
Setup
1.2.3.1.1
1.2.3.1.2
Note:
After entering a parameter, push "
ENTER" and then "SEND".
Confirm the message to switch over to manual operation with "
OK".
Confirm the message to reset to automatic operation also with "
OK".
Only then will the adjustment be stored in the sensor and take effect.
Menu windows are displayed but not
supported by the sensor.
Saving of adjustments carried out here is
therefore not possible.
1.4.3.1.3
1.4.3.1.2
Low:
In case of failure, current output
goes to 22 mA
High:
In case of failure, current output
goes to < 3.6 mA
1.4.3.2
1.4.3.1
}
Off
On
Not used
None
Unknown
Special
Sensor signals measured values only on
request
Sensor signals measured values
unrequested
Choice is not supported
1.4.3.2.3
1.4.3.2.4
Leave the Burst-mode in
OFF position
Choice is not supported
1.2.3.1.1.1
1.2.3.1.2.1
1.4.3.1.3
1.4.3.1.3.1
Generic: D84
Current applied
process value:
97.112
mbar
1 Set as 4 mA value
2 Read new value
3 Leave as found
ABORTENTER
Generic: D84
Current applied
prosess value : 96.262
mbar
1 Set as 20 mA value
2 Read new value
3 Leave as found
ABORT ENTER
Generic: D84
Choose analog output
level
1 4 mA
2 20 mA
3 Other
4 End
ABORTENTER
Generic: D84
WARN - Loop should be
removed from
automatic control
ABORT
OK
Generic: D84
Set the:
1 4 mA
2 20 mA
3 Exit
ABORT ENTER
Generic: D84
Apply new 20 mA input
ABORT
OK
Generic: D84
Current applied
process value: 95.703
mbar
1 Set as 20 mA value
2 Read new value
3 Leave as found
ABORT ENTER
Generic: D84
Set the:
1 4 mA
2 20 mA
3 EXIT
ABORT ENTER
Generic: D84
Apply new 4 mA input
ABORT OK
Generic: D84
Current applied
process value: 96.549
mbar
1 Set as 4 mA value
2 Read new value
3 Leave as found
ABORT ENTER
Generic: D84
AO Alrm typ
Lo
EXIT
Generic: D84
HART output
1 Poll addr
0
2 Num req preams 5
3 Burst mode
Off
4 Burst option
HELP SAVE
HOME
Generic: D84
Analog output
1 AO1
19.920 mA
2 AO Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim
HELP SAVE
HOME
Generic: D84
Fld dev output is
fixed at 4.000 mA
ABBR. OK
Generic: D84
Burst mode
Off
Off
On
Not Used
None
ESC
ENTER
Generic: D84
Burst option
*********
PV
% range/current
Process vars/crnt
HELP
ESC
ENTER