Pressure transmitters D86/D87
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature
15°C … 30°C
- humidity
45 % … 75 %
- air pressure
86 kPa … 106 kPa
Determination of characteristics
limit point adjustment acc. to DIN 16 086
Characteristics
linear
Deviation in characteristics
incl. hysteresis and repeatability
- Turn Down 1 : 1
< 0.25 % with accuracy class 0.25
< 0.1 % with accuracy class 0.1
- Turn Down up to 1 : 5
typ. < 0.3 % with accuracy class 0.25
typ. < 0.1 % with accuracy class 0.1
- Turn Down up to 1 : 10
typ. < 0.4 % with accuracy class 0.25
typ. < 0.2 % with accuracy class 0.1
Influence of the ambient temperature
Average temperature coefficient
of the zero signal
1)
- Turn Down 1 : 1
< 0.15 %/10 K with accuracy class 0.25
< 0.05 %/10 K with accuracy class 0.1
- Turn Down up to 1 : 5
typ. < 0.225 %/10 K with accuracy class 0.25
typ. < 0.075 %/10 K with accuracy class 0.1
- Turn Down up to 1 : 10
typ. < 0.3 %/10 K with accuracy class 0.25
typ. < 0.1 %/10 K with accuracy class 0.1
Long-term stability
Long-term stability of the zero signal
2)
< 0.25 % per 2 years
Other actuating variables
Calibration position
upright, diaphragm points downwards
Influence of the installation position
- D86
< 0,2 mbar
- D87
< 5 mbar
Vibration resistance
mechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2
Product description
1)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C.
2)
Acc. to IEC 770, item 6.3.2 relating to the nominal range.