VEGA D86_D87 Hydrostatic pressure transmitters User Manual

Page 10

background image

10

Pressure transmitters D86/D87

Electrical data

Adjustment ranges

Zero

adjustable from -20 … +95 % of nominal range

Span

adjustable from 3.3 … 120 % of nominal range

Supply and signal circuit (analogue transmission, 4 … 20 mA),
electronics version A, C, I and K

Supply voltage

12 … 36 V DC

permissible residual ripple

U

SS

£ 1 V

- at 100 Hz … 10 kHz

U

SS

£ 10 mV

Output signal
- terminal insert

- analogue transmission (not standardised)

- 4 … 20 mA

- adjustment insert

4 … 20 mA (adjustable)

Current limitation

approx. 22 mA

Fault signal

22 mA (3.6 mA)

Integration time

0 … 10 s

Rise time

70 ms (ti = 0 sec; 0 … 63 %)

Max. permissible load

see load diagram:

Product description

Load in

W

12

300

600

900

18

24

30

36

Supply voltage
in V

Supply and signal circuit (analogue transmission, 4 … 20 mA),
additional data for electronics version L

Supply voltage for pressure transmitters
in conjunction with VEGADIS 12
- without display

12 … 36 V DC

- with display

17 … 36 V DC

Max. input current

150 mA

Current signal range

3.5 … 22 mA

Max. permissible load

see load diagram: