3.2 Wiring plan

Electrical connection

3 Electrical connection

3.1 Wiring instruction

The following wiring plan and the extension examples
1 and 2 are valid for standard as well as for Ex-ver-
sions of the signal conditioning instruments. Please

note the following instructions:
-

the relay contact is shown in unpressurized
condition

-

if strong electromagnetic interferences are ex-
pected, we recommend to use screened cable for

the signal lines

-

the screening must only be earthed at one sensor
side

-

in case of overvoltages we recommend the use of
VEGA-overvoltage arresters

-

the connection must be made according to the
appropriate national installation standards (e.g. in
Germany according to VDE-regulations).

passive voltage input for
connection to the voltage

output of a signal conditioning
instrument (VEGAMET…)

Relay output

Supply voltage

passive current input for
connection of a signal condi-

tioning instrument
(VEGAMET…)

active current input for connec-

tion of a sensor (4 … 20 mA)

Sensor