VEGA VEGASEL 643 User Manual
Page 5
VEGASEL 643
5
Product description
Input 3
1 voltage input
Kind of input
passive two-wire input analog
Range
0/2 … 10 V DC
Inner resistor
Ri
≥
100 k
Ω
Application
direct connection to active voltage output of
e.g. VEGAMET 601, 602 Ex
Switching threshold
adjustable via coded key
Min. hysteresis
1 %
Temperature error
0,05 %/10 K of range
Switch point error
0,5 % of adjusted switch point
Connection cable
2-wire (standard line)
Resistor per conductor
max. 100
Ω
Electrical connection
Screw terminal
max. 1,5 mm
2
Electrical protective measures
Protection
- instrument
IP 30
- terminal socket
IP 20
Protection
II
Overvoltage category
II
Mechanical data
Series
module instrument with terminal socket incl.
transparent cover, cover of the sensor terminals,
coded pin, two connection bridges
Mounting
carrier rail mounting acc. to DIN 46 277, Bl. 3
Dimensions unassembled
W = 36 mm, H = 118,5 mm, D = 134 mm
Weight
appr. 170 g
Ambient conditions
Permissible ambient temperature
-20
°
C … +60
°
C
Storage and transport temperature
-40
°
C … +70
°
C
Relay output
Number
1 output
Contact
1 spdt (open 12 - 13, closed 12 - 14)
AgCdO and Au plated
Turn-on voltage
min. 10 mV DC
max. 250 V AC, 60 V DC
Switching current
min. 10
µ
A DC
max. 2 A AC, 1 A DC
Breaking capacity
max. 125 VA, 54 W
Indicating elements
LED in front plate
green on: operating voltage on
yellow on: relay energized
Functions
Mode
overfill protection (A)
protection against dry running of pumps (B)
Adjustments of the inputs
0 … 20 mA or 4 … 20 mA
0 … 10 V or 2 … 10 V