3 types and versions, 4 technical data and dimensions – VEGA VEGASEL 643 User Manual
Page 4
4
VEGASEL 643
Product description
1.3 Types and versions
VEGASEL 643
Two-point auxiliary level switch with selectable mode; mode A (overfill
protection) or mode B (protection against dry running of pumps)
adjustable switching hysteresis
Inputs:
- passive current input 0/4 … 20 mA
- active current input (connections of a sensor
4 … 20 mA)
- passive voltage input 0/2 … 10 V
Outputs:
1 relay (spdt)
Approvals:
as part of an overfill protection acc. to WHG and
VbF
Application:
level detection, overfill protection,
protection against dry running of pumps
off
on
Level
Time t
Fig. 1.2 Two-point auxiliary level switch
VEGASEL 643
Min.
Max.
1.4 Technical data and dimensions
General data
Power supply
Operating voltage
20 … 250 V AC, 50/60 Hz
20 … 72 V DC
Power consumption
max. 1,7 W (4,5 VA)
Fuse
T 1 A, 250 V
Measuring data inputs
Input 1
1 current input
Kind of input
active two-wire input analog
Range
4 … 20 mA
Application
connection of sensors (4 … 20 mA)
Sensor supply voltage
16 … 24 V DC
Switching threshold
adjustable via coded key
Min. hysteresis
1 %
Current limitation
appr. 25 mA, permanently shortcircuit proof
Temperature error
0,05 %/10 K of range
Switch point error
0,5 % of adjusted switch point
Connection cable
2 wire (standard line)
Resistor per conductor
max. 35
Ω
Interlock diode
for connection of a measuring instrument
max. load 15
Ω
Input 2
1 additional current input
Kind of input
passive two-wire input analog
Range
0/4 … 20 mA
Inner resistor
Ri = 50
Ω
Application
direct connection to active current output of e.g.
VEGAMET 601, 602 Ex
Switching threshold
adjustable via coded key
Min. hysteresis
1 %
Temperature error
0,05 %/10 K of range
Switch point error
0,5 % of adjusted switch point