Pressure transmitter D80
Protective measures
1)
Protection
IP 66, IP 67, IP 68
VEGABOX 01
IP 66 and IP 67
Protection class
III
Overvoltage category
III
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature
15°C … 30°C
- humidity
45 % … 75 %
- air pressure
86 kPa … 106 kPa
Determination of characteristics
limit point adjustment acc. to DIN 16 086
Characteristics
linear
Deviation in characteristics
incl. hysteresis and repeatability
- Turn Down 1 : 1
< 0.25 % with accuracy class 0.25
< 0.1 % with accuracy class 0.1
- Turn Down up to 1 : 5
typ. < 0.3 % with accuracy class 0.25
typ. < 0.1 % with accuracy class 0.1
- Turn Down up to 1 : 10
typ. < 0.4 % with accuracy class 0.25
typ. < 0.2 % with accuracy class 0.1
Influence of the ambient temperature
Average temperature coefficient
of the zero signal
2)
- Turn Down 1 : 1
< 0.15 %/10 K with accuracy class 0.25
< 0.05 %/10 K with accuracy class 0.1
- Turn Down up to 1 : 5
typ. < 0.225 %/10 K with accuracy class 0.25
typ. < 0.075 %/10 K with accuracy class 0.1
- Turn Down up to 1 : 10
typ. < 0.3 %/10 K with accuracy class 0.25
typ. < 0.1 %/10 K with accuracy class 0.1
Long-term stability
Long-term stability of the zero signal
3)
< 0.1 % per 2 years
Other actuating variables
Calibration position
upright, diaphragm points downwards
Influence of the installation position
< 0.2 mbar/20 Pa
Vibration resistance
mechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2
Product description
1)
Maintaining the housing protection IP 66 or IP 67 requires the use of a seal that correctly fits the cable in
the cable entry. If the supplied seal does not fit, a suitable seal must be provided by the customer.
2)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C.
3)
Acc. to IEC 770, item 6.3.2 relating to the nominal range.