Pressure transmitter D80

11

Product description

300

500

700

18

24

30

36

100

Load in

Supply voltage
in V

Supply and signal circuit (analogue transmission, 4 … 20 mA),
additional data for electronics version L

Supply voltage for pressure transmitters
in conjunction with VEGADIS 12
- without display

12 … 36 V DC

- with display

17 … 36 V DC

Max. input current

150 mA

Current signal range

3.5 … 22 mA

Max. permissible load

see load diagram:

Load diagram with display

Supply and signal circuit on VEGA signal conditioning instruments (digital signal
transmission VBUS), additional data for electronics version B

Supply voltage

25 … 36 V DC, from VEGAMET (VBUS) or
from VEGALOG 571 with EV input card

Data transmission

digital (VBUS)

Connection cable

2-wire screened

Cable length

max. 1000 m

Integrated overvoltage protection (option)

Nominal response DC voltage
- protective diode

40 V

- gas separator

650 V

Nominal leakage current
- gas separator

20 kA

Connection cables

Cable entry
- housing

2 x M20x1.5 (for cable ø 5…9mm or 9…12mm)

- external connection housing

2 x M20x1.5 (for cable ø 5…9mm or 9…12mm)

Screw terminals
- sensor

for wire cross-sections of up to 2.5 mm

2

- external connection housing

for wire cross-sections of up to 2.5 mm

2