9.1 Technical data
General data
Series
Module unit for mounting on carrier rail 35x7.5
or 35x15 according to EN 50022
Dimensions
W = 37 mm (1.46 in), H = 68 mm (2.68 in), D =
66 mm (2.6 in)
Weight
approx. 170 g (6 oz)
Housing material
Noryl SE100, Lexan 920A
Voltage supply
Supply voltage
- Standard
200 … 250 V AC, 50/60 Hz
- optional
24 V, 42 V, 48 V, 100 … 130 V AC (+10 %,
-15 %)
Power consumption
1 VA
Sensor input
Quantity
1x level detection or 1x pump control (min./
max.)
Response resistor
1 … 200 kOhm adjustable
Measuring circuit
approx. 12 V eff., max. 1 mA
Switching hysteresis
approx. 20 %
Relay output
Quantity
1 (1x level detection)
Mode
Max. detection or overfill protection
Integration time
approx. 500 ms
Contact
Changeover contact (spdt)
Contact material
AgNi 0.15 hard gold-plated
Turn-on voltage
min. 10 mV DC, max. 250 V AC, 250 V DC
Switching current
min. 10 µA DC, max. 5 A AC, 1 A DC
Breaking capacity
max. 750 VA, max. 54 W
Adjustment elements
Control lamp
to the indication of the relay switching status
Potentiometer
to the adaptation of the product conductivity
18
VEGATOR 256C - Signal conditioning instrument
Supplement
23409
-EN