2 connection procedure – VEGA VEGAWELL 72 4 … 20 mA User Manual
Page 19
I
f potential equalisation currents are expected, the connection
on the processing side must be made via a ceramic capacitor
(
e. g. 1 nF, 1500 V). The low frequency potential equalisation
currents are thus suppressed, but the protective effect against
high frequency interference signals remains.
T
ake note of the corresponding installation regulations for Ex
applications.
5
.2 Connection procedure
P
roceed as follows:
1
W
ire the connection cable up to the connection compart-
ment. The bending radius must be at least 25 mm.
3)
2
C
onnect the wire ends to the screw terminals according to
the wiring plan
P
roceed as follows:
1
S
nap VEGABOX 02 onto the carrier rail or screw it to the
mounting plate
2
L
oosen the cover screws and remove the cover
3
P
ush the cable into VEGABOX 02 through the cable entry
4
L
oosen the screws with a screwdriver
5
I
nsert the wire ends into the open terminals according to
the wiring plan
6
T
ighten the screws with a screwdriver
7
C
heck the hold of the wires in the terminals by lightly
pulling on them
8
T
ighten the compression nut of the cable entry. The seal
ring must completely encircle the cable
9
C
onnect the supply cable according to steps 3 to 8
10 S
crew the housing cover on
T
he electrical connection is finished.
P
roceed as follows:
1
U
nscrew the housing cover
2
I
nsert the connection cable through the cable entry into the
plastic housing
3
L
oosen the screws with a screwdriver
3)
T
he connection cable is already preconfectioned. After shortening the ca-
ble, fasten the type plate with support again to the cable.
Select connec-
tion cable for Ex
applications
Direct connection
Connection via
VEGABOX 02
Via the housing
VEGAWELL
72 • 4 … 20
mA
19
5 C
onnecting to power supply
27501
-
EN
-080806