VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - four-wire User Manual
Page 50
-
TFM-PTFE
hygienically encapsulated,
process seal FKM (Viton)
-25 … +130 °C (-13 … +266 °F)
-
TFM-PTFE
hygienically encapsulated,
process seal EPDM
-40 … +130 °C (-40 … +266 °F)
V
ibration resistance
mechanical vibrations with 4 g and 5 … 100 Hz
10)
Electromechanical data - version IP 66/IP 67
C
able entry
-
D
ouble chamber housing
l
1
x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1
x blind stopper M20 x 1.5; plug M12 x 1 for
VEGADIS
61 (
optional)
or:
l
1
x closing cap ½ NPT, 1 x blind stopper
½
NPT,
plug M12 x 1 for VEGADIS 61
(
optional)
or:
l
1
x plug (depending on the version), 1 x blind
stopper M20 x 1.5; plug M12 x 1 for VEGADIS
61 (
optional)
S
pring-loaded terminals for wire cross-sec-
tion
<
2.5
mm² (AWG 14)
Indicating and adjustment module
V
oltage supply and data transmission
through the sensor
I
ndication
LC
display in dot matrix
A
djustment elements
4
keys
P
rotection rating
-
unassembled
IP
20
-
mounted into the sensor without cover
IP
40
M
aterials
-
H
ousing
ABS
-
I
nspection window
P
olyester foil
Voltage supply
O
perating voltage
-
N
on-Ex and Ex-d instrument
20 … 72 V DC, 20 … 253 V AC, 50/60 H
z
M
ax. power consumption
4 VA; 2.1 W
Electrical protective measures
P
rotection rating
IP
66/IP 67
O
vervoltage category
III
10)
T
ested according to the guidelines of German Lloyd, GL directive 2.
50
VEGAPULS
63 • 4 … 20
mA/HART - four-wire
10 A
nnex
28441
-EN
-120530