beautypg.com

3 coding, Two coded pins in the multipoint connector – VEGA VEGALOG 571 EP (Ex) User Manual

Page 11

background image

on

BA

571EPEx

on

571CPU

5 TE

on

BA

571EPEx

5 TE

1

2

Fig. 1: Min. distances with Ex version
1

Distance to other module cards

2

Distance to the carrier

The distance from the soldered side of the EP(Ex) card to
other module cards must be at least 10 mm (0.393 in). This
distance is ensured by mounting a blind cover with 5 TE width
(= width of the front plate EP card) (detail 1).

If the EP(Ex) card is mounted on the left of the carrier BGT
LOG

571, a blind cover with 5 TE width must be mounted next

to the module of the card (detail 2).

A separating wall between the connection positions of the
intrinsically safe and non-intrinsically safe circuits must be
inserted so that the min. distance of 50 mm (1.97 in) is
maintained. When using an Ex separating chamber (supplied
with the Ex module), the requirement is fulfilled.

With EP Ex module card, protection IP 20 must be maintained.
Gaps and free modules must be covered in front by respective
blind covers

4.3 Coding

A mechanical coding system avoids later interchanging of the
various module cards in the carrier.

The coding system consists of:

l

two coded pins in the multipoint connector

l

two holes in the male multipoint connector of the respective
component

Separation from non-intrinsi-
cally safe circuits

Protection EP Ex-card

VEGALOG

571 EP (Ex) - Input card Profibus PA

11

Mounting

25681

-

EN

-070529