VEGA VEGATOR 521, 522, 523, 527 User Manual
Page 5

VEGATOR
5
Product description
Transistor ouput
Number of
- VEGATOR 521, 522
2 (synchronous switching with relays)
- VEGATOR 523, 527
3 (synchronous switching with relays)
Galvanic separation
floating
Operating voltage
max. 36 V DC
Operating current
max. 60 mA
Transistor voltage loss
U
CE
- 1.5 V
Approvals
VEGATOR 521 Ex, 522 Ex, 523 Ex, 527 Ex
with input in classification
Intrinsic safety
EEx ia IIC, EEx ia IIB
EEx ib IIC, EEx ib IIB
Max. values
U
O
= 20 V
I
K
= 126 mA
P = 626 mW
Characteristics
linear
EEx ia IIC
EEx ia IIB EEx ib IIC EEx ib IIB
Max. permissible external inductance (mH)
0.5 1
1.5
2
2
9
Max. permissible external capacitance (nF)
97
78
68
486
200
1000
The intrinsically safe circuits are reliably (galvanically) separated from the non-intrinsically
safe circuits up to a peak value of the nominal voltage of 375 V.
On instruments with 2 channels (VEGATOR 527 Ex) the intrinsically safe circuits are reliably
separated.
CE conformity
VEGATOR 521 Ex, 522 Ex, 523 Ex and 527 Ex signal conditioning instruments meet the
protective regulations of EMC (89/336/EW) and NSR (73/23/EWG). Conformity has been
judged acc. to the following standards:
EMC
Emission
EN 50 081 - 1: 1993
Susceptibility
EN 50 082 - 2: 1995
NSR
EN 61 010 - 1: 1993