beautypg.com

Diagnosis checking the electrical components – VEGA VEGABAR 24 User Manual

Page 22

background image

22

VEGABAR 24

Voltage
- the terminal voltage on VEGABAR must be

at least 12 V DC

Current

Current value

Condition

3,8 … 20,6 mA

standard range for output current

0 mA

signal line open circuit

< 3,6 mA

oscillator or pressure sensor ele-
ment defect

> 21,6 mA

short-circuit in the signal line,
oscillator or pressure sensor ele-
ment defective

Diagnosis

Checking the electrical components

~

1 2 3

+

+

mA

Voltage

Current

V

External
energy source

Current meter for
local control

mA