beautypg.com

VEGA VEGABAR 75 4 … 20 mA_HART User Manual

Page 20

background image

4

E

mpty the vessel or reduce process pressure

5

S

et a current of 4 mA with the [+] and [-] keys

6

M

eas. range end: Set rotary switch to "span"

7

F

ill the vessel or increase process pressure

8

S

et a current of 20 mA with the [+] and [-] keys

9

O

peration: Set rotary switch to "OPERATE"

10 C

lose housing cover

T

he adjustment data are effective, the output current 4 … 20 mA

corresponds to the actual level.

P

roceed as follows for the adjustment of the integration time

with VEGADIS 12:

1

O

pen housing cover

2

S

et rotary switch to "ti"

3

B

y pushing the [-] key 10-times, make sure that the

integration time is set to 0 sec.

4

F

or every 1 sec. requested integration time, push the [+]

key once.

5

T

he integration time is the time required by the output

current signal to reach 90 % of the actual height after a
sudden level change.

6

S

et rotary switch to "OPERATE"

7

C

lose housing cover

T

he display outputs the current 4 … 20 mA as bar graph and

digital value.

W

ith 4 mA no segment of the bar graph appears, with 20 mA

all segments appear. This assignment is fix.

Y

ou can scale the digital value to any value between -9999 …

+

9999

via the adjustment module.

P

roceed as follows for scaling the indication of VEGADIS 12:

1

O

pen housing cover

2

I

nitial value: Set rotary switch to "zero"

3

S

et the requested value, e.g. 0 with the [+] and [-] keys

4

F

inal value: Set the rotary switch to "span"

5

S

et the requested value, e.g. 1000 with the [+] and [-] keys

6

D

ecimal point: Set the rotary switch to "point"

7

W

ith the [+] and [-] keys you can adjust the requested

value, e.g. 8888 (no decimal point)

Adjustment steps, integration
time

Adjustment steps, scaling

20

VEGABAR

75 - 4 … 20

mA/HART

S

et up

28433

-EN

-070718