Setting of parameters of vegascan 850 in rtu mode – VEGA VEGASCAN 850 Modbus signal output User Manual
Page 8
8
Modbus signal output VEGASCAN 850
Start
Slave
ad-
dress
Func-
tion
code
Address of the
1. register
word
Number of
register
words
Error
Check
End
No. of
bytes
Value
range
Meaning
Structure of the measured value enquiry Modbus master to VEGACOM 557
RTU enquiry telegram acc. to measured values (function code 04)
3 ... 4
1
1
2
2
2
3 ... 4
Closed level
1 .. 247 04
0 ... 65.509
1 ... 127
CRC
Closed level
0x01
0x04
0x00
0x1C
0x00
0x02
0xXX
0xXX
Start
Func-
tion
code
No.of
data
bytes
Error
Check
End
No. of
bytes
Value
range
Meaning
Structure of the answer VEGACOM 557 to Modbus master
RTU answer telegram (function code 04)
3 ... 4
1
1
1
2 bytes per
register word
2
3 ... 4
Closed level
1 .. 247
04
2 ....
255
0 ... 255 per byte
CRC
Closed level
0x01
0x04
0x04
0x01
0x4A
0x00
0x00
0xXX
Data (DCS values)
0xXX
DCS value 15 of VEGASCAN:
Status:
0x00
Meas. unit:
0x00
Measured value:
0x014A = 3.30%
Data transmission with Modbus RTU
Setting of parameters of VEGASCAN 850 in RTU mode
Various parameters of VEGASCAN can be enquired measurement loop-related.
The following list gives an overview of the parameters involved:
Parameter name
possible access mode
Integration time
reading
writing
Scaling (0 %)
reading
writing
Scaling (100 %)
reading
writing
The enquiry or modification of parameters via the Modbus is made with the function codes 16
(= Preset Multiple Registers) and 04 (Read Input Registers).
Slave
ad-
dress