beautypg.com

VEGA VEGASWING 83A User Manual

Page 9

background image

VEGASWING 81A and 83A

9

Approvals VEGASWING 80 A

WHG

Approval as overfill protection acc. to WHG
Ambient temperature on the housing

-40°C … +70°C

Product temperature

-40°C … +100°C

- test report Z-65.11-154

VEGASWING 81A EX/83A EX with oscillator

SWING E82Z EX and suitable signal
conditioning instrument

- test report Z-65.11-163

VEGASWING 81A EX / 83A EX with oscillator

SWING E82 C, R, T

- with temperature adapter

up to 150°C

Operating pressure

max. 40 bar

Recurring test acc. to WHG

According to the type approval to WHG (Z-65.11-154) the recurring test acc. to WHG can
be carried out by pr essing the test key on the VEGA TOR 536 EX, 537 EX, 636 EX signal
conditioning instrument. The sensor must not be removed, nor can a response be trig-
gered by filling the vessel. This is valid for VEGASWING 81 A EX and 83 A EX with two-wire
oscillator SWING E82 Z EX.

Explosion protection VEGASWING 81A EX0, 83A EX0

Certificate

EU-type approval certificate acc. to ATEX 100 a
TÜV 98 ATEX 1320 X

Classification mark

II 1 G EEx ia IIC T6

Permissible application range

Ex Zone 1, Ex Zone 0

Ambient temperature dependent on temperature class and Ex-Zone:
see EU-type approval certificate
Electrical safety characteristics:
see EU-type approval certificate

Oscillators

C - Non-contact switch (SWING E82 C)

Supply voltage

20 … 250 V AC, 50/60 Hz or 20 … 250 V DC

Output

non-contact switch

Current consumption

approx. 3 mA (via the load circuit)

Load current

min. 10 mA
max. 400 mA (at I > 300 mA the ambient
temperature can be max. 60°C)
max. 4 A to 40 ms (not WHG specified)

Protection class

I

Overvoltage category

III

Modes

A: max. level detection, overfill protection
B: min. level detection, dry run protection

Product description