Pressure transmitters D76 and D77
Measuring ranges
Nominal meas. range
Gauge pressure
Low pressure
Pressure transmitters
resistance
resistance
D76
D77
D76 / D77
Gauge pressure
0 … 0.1 bar
10 bar / –
-0.1 bar
•
–
0 … 0.2 bar
15 bar / –
-0.2 bar
•
–
0 … 0.4 bar
20 bar / 10 bar
-0.4 bar
•
•
0 … 1.0 bar
25 bar / 25 bar
-1.0 bar
•
•
0 … 2.5 bar
35 bar / 25 bar
-1.0 bar
•
•
0 … 5.0 bar
45 bar / 25 bar
-1.0 bar
•
•
0 … 10.0 bar
60 bar / 25 bar
-1.0 bar
•
•
0 … 20.0 bar
90 bar / 25 bar
-1.0 bar
•
•
Zero
-20 % … +95 % of nominal measuring range
adjustable
Span
3.3 % … 120 % of nominal measuring range
adjustable
Recommended turn down with
accuracy class 0.25
up to 1 : 5
Adjustment elements
Pressure transmitters
- terminal insert
without adjustment elements
- adjustment insert
2 keys, 1 rotary switch
Measuring accuracy (similar to DIN 16 086, DIN V 19 259-1 and IEC 770)
Deviation
Reference conditions acc. to IEC 770
- temperature
15°C … 35°C
- moisture
45 % … 75 %
- air pressure
860 mbar … 1060 mbar
Determination of characteristics
limit point adjustment acc. to DIN 16 086
Characteristics
linear
Deviation in characteristics
1)
< 0.25 % with accuracy class 0.25
Hysteresis
1)
< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell
Repeatability
1)
< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell
Influence of the ambient temperature in general
Average temperature coefficient
of the zero signal
1) 2)
< 0.15 %/10 K with accuracy class 0.25
Product description
1)
Relating to the nominal measuring range.
2)
In the compensated temperature range of 0°C … +80°C, reference temperature 20°C.