beautypg.com

VEGA D77 Hydrostatic pressure transmitters User Manual

Page 8

background image

8

Pressure transmitters D76 and D77

Measuring ranges

Nominal meas. range

Gauge pressure

Low pressure

Pressure transmitters

resistance

resistance

D76

D77

D76 / D77

Gauge pressure
0 … 0.1 bar

10 bar / –

-0.1 bar

0 … 0.2 bar

15 bar / –

-0.2 bar

0 … 0.4 bar

20 bar / 10 bar

-0.4 bar

0 … 1.0 bar

25 bar / 25 bar

-1.0 bar

0 … 2.5 bar

35 bar / 25 bar

-1.0 bar

0 … 5.0 bar

45 bar / 25 bar

-1.0 bar

0 … 10.0 bar

60 bar / 25 bar

-1.0 bar

0 … 20.0 bar

90 bar / 25 bar

-1.0 bar

Zero

-20 % … +95 % of nominal measuring range
adjustable

Span

3.3 % … 120 % of nominal measuring range
adjustable

Recommended turn down with
accuracy class 0.25

up to 1 : 5

Adjustment elements

Pressure transmitters
- terminal insert

without adjustment elements

- adjustment insert

2 keys, 1 rotary switch

Measuring accuracy (similar to DIN 16 086, DIN V 19 259-1 and IEC 770)

Deviation

Reference conditions acc. to IEC 770
- temperature

15°C … 35°C

- moisture

45 % … 75 %

- air pressure

860 mbar … 1060 mbar

Determination of characteristics

limit point adjustment acc. to DIN 16 086

Characteristics

linear

Deviation in characteristics

1)

< 0.25 % with accuracy class 0.25

Hysteresis

1)

< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell

Repeatability

1)

< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell

Influence of the ambient temperature in general

Average temperature coefficient
of the zero signal

1) 2)

< 0.15 %/10 K with accuracy class 0.25

Product description

1)

Relating to the nominal measuring range.

2)

In the compensated temperature range of 0°C … +80°C, reference temperature 20°C.