beautypg.com

VEGA D77 Hydrostatic pressure transmitters User Manual

Page 19

background image

Pressure transmitters D76 and D77

19

Setup

Adjustment information:

- A modification of zero does not influence

the adjusted span.

- It is also possible to adjust currents for

partial fillings, e.g. 8 mA for 25 % and
16 mA for 75 %. Then the electronics auto-
matically calculates the current values for
0 % and 100 % (only possible with a differ-
ence

³ 3.3 %).

- If the current values react to the key press-

ing with a time delay, there can be two
reasons:
- the last adjustment was carried out with a

level deviating considerably from the
actual level.

Integration time

For damping level fluctuations, an integration
time ti of 0 … 10 sec. can be adjusted.

Adjust integration time

• Set rotary switch to "ti“.
• By pressing the "-“ key 10 times make sure

that the integration time is set to 0 sec.

• Per 1 sec. requested integration time, the

"+“ key has to be pushed once.

The integration time is the time required by
the current output signal to reach 90 % of the
actual level after a sudden change of the
level.