2 terminal assignment, 20ma, Electronics version a – VEGA D77 Hydrostatic pressure transmitters User Manual
Page 15: Electronics version c, Electronics version d, Electronics version e, Electrical connection, Direct cable outlet, 4 … 20 ma output signal, 4 … 20 ma output signal with integrated adjustment
Pressure transmitters D76 and D77
15
Electrical connection
br
bl
ge
+
-
Direct cable outlet
-
+
-
+
5
1 2 3 4
terminal
Klemmeinsatz
VEGA-signal conditioning instruments
VEGA-Auswertger
ä
te
For connection to
Zum Anschluss an
+
-
Control instrument
(5 … 19 mA measure-
ment)
Breather capillaries
Suspension
cable
only used in conjunction with
VEGADIS 12, if not used,
connect to minus
Screen
12 … 36 V DC
for supply or to the process-
ing system (4 … 20 mA)
Supply or for evaluation
of VEGAMET signal
conditioning instrument
12 … 36 V DC
-
+
-
+
+
-
12V...36V DC
4...20mA
Bedieneinsatz
operating unit
S
Z
t
i
Op
4
3
2
1
5
Electronics version A
5 … 19 mA output signal for connection to
VEGA signal conditioning instruments
Electronics version C
4 … 20 mA output signal
Electronics version D
4 … 20 mA output signal with integrated
adjustment
Electronics version E
4 … 20 mA output signal with operatability
from VEGADIS 12
5
1 2 3 4
4-20mA
terminal
Klemmeinsatz
+
-
12V...36V DC
4...20mA
-
+
-
+
Control instrument
4 … 20 mA
Power supply
12 … 36 V DC
Control instrument
4 … 20 mA
Power supply
12 … 36 V DC
-
+
5
1 2 3 4
VEGADIS 12
Zum Anschluss an
For connetction to
+
-
12V...36V DC
terminal
Klemmeinsatz
for indicating instru-
ment VEGADIS 12
Terminal assignment
Ground, cable screen
1
Power supply [+]
2
Power supply [–]
3
Control instrument [–] / VEGADIS 12
4
not assigned, connect via wire bridge
5
not assigned, connect via wire bridge
ergy) must not connected in series. The
special installation regulations (DIN VDE
0165) must be observed.
Pressure transmitters in certain versions are
equipped with a warning label, informing of
measures to be taken to avoid electrostatic
discharge. Keep the contents of the warning
label in mind.
Connection cable
Make sure that the connection cable is speci-
fied for the expected operating temperatures
in your systems. The cable must have an
outer diameter of 5 … 9 mm. Otherwise the
seal effect of the cable connection will not be
ensured.
Cables for intrinsically safe circuits must be
marked with a blue colour and must not be
used for other circuits.
4.2 Terminal assignment
ge