Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has three (3) C19 outlets.
P
O W E R
C O R D
— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 60 A plug.
H579N
Electrical
Input connection
IEC-309 60 A cord included
Acceptable input voltage
200–240 VAC +6% to -10%
Maximum input current (phase)
60 A (48 A UL(C-UL) derated)
Input frequency
50/60 Hz
Output voltage
200–240 VAC +6% to -10%
Output connections
(3) C19
Maximum output current (outlet)
C19; 16 A (UL(C-UL) derated)
Maximum output current (phase)
48 A
Maximum output current (bank)
16 A (UL(C-UL) derated)
Overcurrent protection (internal)
(3) 20 A 2-pole breakers
Cord length
3.65 m (12.00 ft)
Physical
Dimensions
(H x W x D)
38.81 x 4.36 x 12.57 cm
(15.28 x 1.72 x 4.95 in)
Shipping dimensions
(H x W x D)
50.01 x 39.49 x 19.50 cm
(19.69 x 15.55 x 7.68 in)
Weight
6.92 kg (15.22 lb)
Shipping weight
9.80 kg (21.56 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals
UL(C-UL)
ROHS
Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision